PLEASE PAY ATTENTION ABOUT THE CONNECTIONS BETWEEN OUTPUT SIGNAL OF THE MOTOR AND THE PLC !

OUTPUTS ARE NOT PROTECTED AGAINST EXCESSIVE CURRENT REQUEST (MAX 100mA).

IF THE OUTPUTS WILL BE CONNECTED TO GROUND OR LOW RESISTANCE LOAD WHEN THE MOTOR IS ENABLED THE OUTPUT PNP TRANSISTOR WILL BE DAMAGED PERMANENTLY.

Input signals

the inputs are protected from inversion and overvoltage. The logic level is 24VDC.

io_sig.jpg

Output Signals

PNP - Default type (Default type)

The digital output signals are by default PNP type (without internal pull-down).
The absolute current capability is 100mA per output lines.

io_sig_2.jpg

NPN Type (only on request)

io_sig_1.jpg